DCA 11000/DCA 11000 WH Series Dehumidifiers
Performance |
 |
 |
 |
Features
- MET Laboratory Safety Listed To UL 1995
- 3 Year Parts Warranty
- Dual Refrigeration Circuit Construction
- Dual Copeland Scroll Compressors
- Motorized Evaporator By-Pass Control
- Low Ambient Head Pressure Control
- Rifle Tube Refrigeration Coils
- TEFC Blower Motor
- Stainless Steel Condensate Drain Pan
- Standard Microprocessor Control System
- Water Cooled Condenser For Water Heating Or A/C Available
- Many Other Options Available
room heating while dehumidifying (see specifications).
|
| Performance |
82DB / 50% R.H. |
82DB / 60% R.H. |
Notes |
| Moisture Removal LB/HR |
110.5 |
139.8 |
1 |
| Sensible Cooling, MBH |
172.0 |
156.9 |
2 |
| Net Reheat, MBH |
188.9 |
222.2 |
3 |
| Water Heating - A, MBH |
133.3 |
139.7 |
4,6 |
| Water Heating - B, MBH |
234.6 |
245.9 |
4,6 |
|
Notes: 1. Reheat mode assuming 1050 BTU/lb. 2. Cooling mode with remote air cooled condenser at 95°F ambient. 3. Defined as sum of latent and compressor input. Use Dehumidifier for supplemental heat only. 4. Assuming 80°F entering water temperature. 5. For conditions and data not shown contact the Factory. 6. For pool water usually only circuit A is required. |
Diagrams |
 |
 |
| DCA11000 |
| A |
136 1/2 |
G |
25 1/2 |
M |
69 |
| B |
77 |
H |
70 1/2 |
N |
127 |
| C |
72 |
I |
60 1/4 |
- |
- |
| D |
30 |
J |
3 |
- |
- |
| E |
30 |
K |
4 |
- |
- |
| F |
18 |
L |
9 1/2 |
- |
- |

Design Specifications |
| Electrical |
208/230V |
460V |
575V |
| Phase/Hz |
3/60 |
3/60 |
3/60 |
| Compressor M.B.H. A/B |
108/190 |
108/190 |
108/190 |
| Compressor RLA A/B |
34.3/55.2 |
17.5/27.2 |
13.2/24.3 |
| Compressor LRA A/B |
232/425 |
125/187 |
100/148 |
| Blower Motor H.P. |
7.5 |
7.5 |
7.5 |
| Blower Motor FLA |
19.8 |
9.9 |
7.8 |
| Unit FLA |
98.8 |
48.7 |
40.1 |
| Maximum Fuse Size |
150 |
80 |
70 |
| Minimum Circuit Ampacity |
124.9 |
62.4 |
52.3 |
| Operating kW |
27.1 |
27.1 |
27.0 |
|
| CFM: 10,850 |
DCA11000 Weight: 4,760 lbs.* |
| External Static Pressure: 0.50" H2O |
Water Inlet O.D. A/B: 1.375/1.625 |
| Refrigerant: R-22 Charge A/B 55lbs/80lbs |
Water Outlet O.D. A/B: 1.375/1.625 |
| Compressor Type: Scroll |
Water Flow G.P.M. A/B: 17.0/36.0 |
| Filter 9 Each: 20" x 24" x 4" pleated |
Pressure Drop (Ft. Wc) A/B: 6.7/12.4 |
| Drain Connection: 1" Bar Drain |
|
* Weight shown is for basic unit with no options. Contact factory for weight with options needed. Above data based on 50% RH + Return Air 82°F and Pool Water at 80°F |
|
Other Information |
| Options: (Consult Factory) |
- Right Side Component Access - Top or Bottom Discharge - Extended Surface Filters 2" & 4" - Outdoor Installation Package |
- Outdoor Air Assembly with Damper & Filter Make Up - External Static Upgrade - Heresite Coated Coils |
- Motorized Bypass Damper - Remote Ready Delete - Defrost Timer Package - Other
|
CAUTIONS: The reheat capacity rating includes latent recovery and heat of compression. It is recommended that dehumidifiers be used for supplemental heat only.
The cooling capacity is based on an ambient temperature of 95°F. As outside conditions vary, so will the performance of the dehumidifier.
ALL PRINTED INFORMATION SHOWN SUBJECT TO CHANGE WITHOUT NOTICE |
Back to Top
|

|